Islanding detection during intended island operation of nested microgrid

IEEE
Konferenssijulkaisu
vertaisarvioitu
article
Osuva_Laaksonen_Hovila_2018.pdf - Hyväksytty kirjoittajan käsikirjoitus - 6.84 MB

Kuvaus

In the future, functionalities like islanding detection must also operate during intended island operation of (MV+MV or MV+LV) nested microgrids. In this paper, healthy and faulty islanding detection of LV network connected generation unit during nested (MV+LV) microgrid islanded operation were studied by simulations with PSCAD model from real-life smart grid pilot. Main focus in the simulations was on the study and comparison of usage possibilities of combined (high-speed communication based transfer trip & fault detection/direction + voltage vector shift) and multi-criteria (voltage total harmonic distortion & voltage unbalance) based islanding detection schemes also during intended island operation of nested microgrid consisting only from inverter based generation units.

Emojulkaisu

ISBN

978-1-5386-4505-5

ISSN

2165-4824
2165-4816

Aihealue

Sarja

IEEE PES Innovative Smart Grid Technologies Conference Europe

OKM-julkaisutyyppi

A4 Artikkeli konferenssijulkaisussa