Identifcation and Location of Partial Discharge Defects in Medium Voltage AC Cables
annif.suggestions | cables|electrical engineering|measuring methods|power lines|signal processing|voltage|insulations (building supplies)|condition monitoring|pulse|electrical power networks|en | en |
annif.suggestions.links | http://www.yso.fi/onto/yso/p188|http://www.yso.fi/onto/yso/p1585|http://www.yso.fi/onto/yso/p20083|http://www.yso.fi/onto/yso/p20336|http://www.yso.fi/onto/yso/p12266|http://www.yso.fi/onto/yso/p15755|http://www.yso.fi/onto/yso/p19601|http://www.yso.fi/onto/yso/p15423|http://www.yso.fi/onto/yso/p3751|http://www.yso.fi/onto/yso/p7753 | en |
dc.contributor.author | Shafiq, Muhammad | |
dc.contributor.author | Robles, Guillermo | |
dc.contributor.author | Hussain, Amjad | |
dc.contributor.author | Kauhaniemi, Kimmo | |
dc.contributor.author | Lehtonen, Matti | |
dc.contributor.department | fi=Ei tutkimusalustaa|en=No platform| | - |
dc.contributor.faculty | fi=Tekniikan ja innovaatiojohtamisen yksikkö|en=School of Technology and Innovations| | - |
dc.contributor.orcid | https://orcid.org/0000-0002-2272-0899 | - |
dc.contributor.orcid | https://orcid.org/0000-0002-7429-3171 | - |
dc.contributor.organization | fi=Vaasan yliopisto|en=University of Vaasa| | |
dc.date.accessioned | 2020-12-08T12:13:38Z | |
dc.date.accessioned | 2025-06-25T12:52:40Z | |
dc.date.available | 2020-12-08T12:13:38Z | |
dc.date.issued | 2019-08-05 | |
dc.description.abstract | The presence of partial discharge (PD) in electrical equipment is the confirmation or indication of an ongoing degradation of its dielectric insulation. PD study is a widely used tool for condition monitoring of medium voltage (MV) cables. The location of the defects can be considered as one of the most important tasks of diagnosis in underground installations of MV cables. A lot of references can be found on the location of single PD sources along the cable. However, several PD defects can be active simultaneously along a cable section. This paper presents an experimental study on a MV cable having two PD sources and noise. Adopting one end measurement technique, a high frequency current transformer (HFCT) is used to capture the PD current pulses. A simple approach of identification of the PD signals originated from different PD sources is presented based on wave-shape study along with a time domain reflectometry analysis. The presented measurement methodology and time domain analysis technique provides a convenient way for detection and location of more than one PD sources along a cable section. | - |
dc.description.notification | © 2019 Nordic Insulation Symposium. | - |
dc.description.reviewstatus | fi=vertaisarvioitu|en=peerReviewed| | - |
dc.format.bitstream | true | |
dc.format.content | fi=kokoteksti|en=fulltext| | - |
dc.format.extent | 6 | - |
dc.format.pagerange | 22-27 | - |
dc.identifier.olddbid | 13127 | |
dc.identifier.oldhandle | 10024/11735 | |
dc.identifier.uri | https://osuva.uwasa.fi/handle/11111/1069 | |
dc.identifier.urn | URN:NBN:fi-fe2020120899862 | - |
dc.language.iso | eng | - |
dc.publisher | Nordic Insulation Symposium | - |
dc.relation.conference | Nordic Insulation Symposium on Materials, Components and Diagnostics (NORD-IS) | - |
dc.relation.doi | 10.5324/nordis.v0i26.3269 | - |
dc.relation.ispartofseries | Proceedings of the Nordic Insulation Symposium | - |
dc.relation.issn | 2535-3969 | - |
dc.relation.numberinseries | 26 | - |
dc.relation.url | https://doi.org/10.5324/nordis.v0i26.3269 | - |
dc.source.identifier | https://osuva.uwasa.fi/handle/10024/11735 | |
dc.subject.discipline | fi=Sähkötekniikka|en=Electrical Engineering| | - |
dc.title | Identifcation and Location of Partial Discharge Defects in Medium Voltage AC Cables | - |
dc.type.okm | fi=A4 Artikkeli konferenssijulkaisussa|en=A4 Peer-reviewed article in conference proceeding|sv=A4 Artikel i en konferenspublikation| | - |
dc.type.publication | article | - |
dc.type.version | publishedVersion | - |
Tiedostot
1 - 1 / 1
Ladataan...
- Name:
- Osuva_Shafiq_Robles_Hussain_Kauhaniemi_Lehtonen_2020.pdf
- Size:
- 1.32 MB
- Format:
- Adobe Portable Document Format
- Description:
- Artikkeli