Combined Islanding Detection Scheme Utilizing Active Network Management for Future Resilient Distribution Networks
Pysyvä osoite
Kuvaus
Needed new cost-efficient, reliable, standardised and redundant solutions for future resilient smart grids must utilise possibilities of advanced ICT technologies (such as wireless fifth generation and cloud servers with smart big data analytics) and have cyber-security integrated into all solutions. In this study, resilient, future-proof, grid-code compatible combined islanding detection scheme for medium-voltage (MV) and low-voltage network connected distributed generation units during grid-connected operation is simulated. The utilisation of active network management functionality at the MV level enables to control the reactive power unbalance continuously in order to ensure reliable islanding detection without a non-detection zone. The combined scheme also prevents maloperations due to other disturbances.
Emojulkaisu
ISBN
ISSN
2051-3305
Aihealue
Kausijulkaisu
The Journal of Engineering|2018
OKM-julkaisutyyppi
A1 Alkuperäisartikkeli tieteellisessä aikakauslehdessä