Characterization of Corona and Internal Partial Discharge under Increasing Electrical Stress using Time Domain Analysis
Shafiq, Muhammad; Kiitam, Ivar; Taklaja, Paul; Hussain, Amjad; Kütt, Lauri; Kauhaniemi, Kimmo (2020-08-05)
Shafiq, Muhammad
Kiitam, Ivar
Taklaja, Paul
Hussain, Amjad
Kütt, Lauri
Kauhaniemi, Kimmo
IEEE
05.08.2020
Julkaisun pysyvä osoite on
https://urn.fi/URN:NBN:fi-fe202102023542
https://urn.fi/URN:NBN:fi-fe202102023542
Kuvaus
vertaisarvioitu
© 2020 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.
© 2020 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.
Tiivistelmä
Aging and abnormal stresses accelerate insulation degradation and reduce the lifetime of power equipment. Partial discharge (PD) measurement is an effective tool to study the condition of the insulation. Reliability of PD diagnosis depends on the accurate interpretation of the measured PD signals. PD itself is a complex phenomenon and the presence of different types of discharge sources makes interpretation of the PD data quite challenging. This paper investigates internal and corona PDs in order to distinguish them when both are active simultaneously. The presented work identifies the PD sources based on time domain analysis that provides a simplified solution as compared to identification techniques based on different statistical features leading to complex data processing. While superimposed phase-resolved partial discharge (PRPD) patterns provided incomplete information, time domain PD characteristics e.g. pulse repetition rate and pulse amplitude combined with PRPD mapping are analyzed to differentiate PD activity. Furthermore, the electrical stress (voltage level) is increased gradually in the experiments made and PD behavior is studied. The presented technique contributes to enhancing the accuracy of PD diagnosis that is necessary for appropriate decision making concerning the repair of affected components.
Kokoelmat
- Artikkelit [2798]