Non-Directional Earth Fault Passage Indication in Isolated Neutral Distribution Networks
Farughian, Amir; Kumpulainen, Lauri; Kauhaniemi, Kimmo (2020-09-11)
Farughian, Amir
Kumpulainen, Lauri
Kauhaniemi, Kimmo
MDPI
11.09.2020
Julkaisun pysyvä osoite on
https://urn.fi/URN:NBN:fi-fe2020101484109
https://urn.fi/URN:NBN:fi-fe2020101484109
Kuvaus
vertaisarvioitu
© Writers. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license, http://creativecommons.org/licenses/by/4.0/
© Writers. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license, http://creativecommons.org/licenses/by/4.0/
Tiivistelmä
In this paper, two new methods for locating single-phase to ground faults in isolated neutral distribution networks are proposed. The methods are based on the analysis of symmetrical sequence currents. They are solely based on currents, not requiring voltage measurement. The first method employs only the zero sequence current and the second one utilizes the negative sequence current in combination with the zero sequence current. It is revealed why using only zero sequence current with a simple threshold is insufficient and may lead to false results. Using the proposed methods, earth faults with high resistances can be located in isolated neutral distribution networks with overhead lines or cables.